EMC Directive in Control Cabinet Construction: Requirements, Standards, and Documentation Requirements

As a manufacturer of switchgear with over 50 years of experience, we’ve compiled everything you need to know about the EMC Directive in switchgear construction on this page—explained in an easy-to-understand way and organized with practical applications in mind.

  • ✓The EMC Directive Explained Simply
    Legal basis, scope, and protection objectives clearly outlined
  • ✓Safety & Legal Certainty
    Properly Implementing Conformity Assessment, CE Marking, and Documentation
  • ✓Practical knowledge from 50 years of experience
    Straight from our switchgear experts

The EMC Directive 2014/30/EU is the central EU legal act governing electromagnetic compatibility and is of fundamental importance for control cabinet construction. The basic principle is that equipment must function as intended in its electromagnetic environment without causing unacceptable interference to other devices. This gives rise to two core requirements: limited emission of interference and sufficient immunity to interference. The current directive replaced the previous Directive 2004/108/EC and was transposed into national law in Germany through the Act on the Electromagnetic Compatibility of Equipment (EMVG).

This page is intended for design engineers and procurement professionals in the plant and machinery engineering sectors and covers legal foundations, scope of application, technical protection objectives, harmonized standards, the conformity assessment process, responsibilities, and market surveillance. Important for practical application: Switchgear assemblies are generally subject to both the Low-Voltage Directive 2014/35/EU—applicable to rated voltages between 50 V AC and 1000 V AC or 75 V DC and 1500 V DC – as well as the requirements for the electromagnetic environment. These are therefore not mutually exclusive requirements, but rather complementary ones that are jointly met when applying harmonized standards such as DIN EN IEC 61439.

Your contact persons

Dirk Schütz

Head of Switchgear Construction Department

T +49 2261 987-405
E-Mail | vCard

Felix Trommershausen

Sales Switchgear Construction

T +49 2261 987-413
E-Mail | Linkedin | vCard

Legal Basis: Directive 2014/30/EU and the German EMVG

Directive 2014/30/EU is systematically organized into essential requirements, which are set forth in Annex I, and conformity assessment procedures, as outlined in Annexes II and III. It thus follows the structure of the New Legislative Framework, the common framework for European product harmonization, and establishes obligations for manufacturers, authorized representatives, and importers. National implementation is carried out through the EMVG, which contains its own definitions and regulates the responsibilities of the market surveillance authority. For control panel manufacturing, the relationship to other legal acts is also relevant: The Low Voltage Directive 2014/35/EU often applies in parallel; it applies to electrical equipment with a rated voltage range between 50 V AC and 1,000 V AC or 75 V DC and 1,500 V DC. If the control cabinet performs safety-related control functions, the Machinery Directive 2006/42/EC also applies. These legal acts complement each other in their safety objectives but do not replace one another—for CE marking, all relevant requirements must be met cumulatively.

Structure and Basic Requirements of Directive 2014/30/EU

Annex I of Directive 2014/30/EU sets forth the essential requirements upon which the entire framework is based: Equipment must generate electromagnetic disturbances only to an extent that does not impair the intended operation of radio and telecommunications equipment or other equipment, and must at the same time exhibit adequate immunity to external electromagnetic influences. The text of the Directive deliberately avoids specifying concrete numerical values—this technology-neutral wording leaves the establishment of a specific limit value to harmonized standards, such as the DIN EN 61000-6 series. In addition, the recitals set forth the objective of protecting the internal market, while subsequent chapters define the scope of application—which covers all equipment that can cause electromagnetic interference or be affected by it— as well as the notification of notified bodies and market surveillance by the competent national authorities. If a piece of equipment meets these requirements, the manufacturer affixes the CE marking, thereby publicly confirming its conformity. A special provision applies to fixed installations: Because they are individually installed at the site of operation, they are subject to separate requirements that differ from the conformity assessment for mass-produced equipment, which generally requires technical documentation at the installation site.

Implementation in Germany: EMVG and the Federal Network Agency

The EMVG specifies the European requirements of Directive 2014/30/EU specifically for the German legal system, without deviating from the substance of its protective objectives. It defines the scope of application as well as key terms such as devices, equipment, and fixed installations, and establishes the obligations of economic operators—manufacturers, authorized representatives, importers, and distributors. As the competent market surveillance authority, the Federal Network Agency monitors compliance with these requirements, thereby supplementing—but not replacing—the European conformity assessment. It has extensive powers to conduct inspections and request information; it may enter business premises, inspect documents, and demand technical evidence to verify compliance on a random basis. If violations are detected, it has a range of measures at its disposal: from requests for corrective action to recall orders and bans on the sale of non-compliant products. Violations of labeling, documentation, or cooperation obligations are classified as administrative offenses and may be punished with a fine, the amount of which depends on the severity of the violation and is set within the limits established by law. The key point remains: The EMVG does not create any independent, deviating requirements, but rather implements the provisions of EU law in a binding and enforceable manner, thereby ensuring a uniform, reliable framework for conformity and market surveillance in Germany.

Distinction from the Radio Equipment Directive and Sector-Specific Regulations

Not all equipment with electromagnetic relevance is subject to the EMC Directive 2014/30/EU: Instead, radio equipment falls under the Radio Equipment Directive 2014/53/EU, which already incorporates EMC requirements as separate essential requirements and thus precludes the parallel application of the EMC Directive. For control panel construction, this distinction is relevant in practice as soon as Wi-Fi, Bluetooth, or cellular modules are installed in the system—this can affect the legal classification of the entire switchgear and must be clarified before the conformity assessment process begins. Other sector-specific exemptions include, for example, motor vehicles under UN/ECE R10, medical devices under the MDR, and specific equipment for aviation, rail, and maritime transport, each of which is subject to its own regulatory frameworks with integrated EMC provisions. Even equipment with system-related, non-critical EMC behavior may fall outside the scope of application. A clear product classification at the start of the project is therefore essential to determine which regulatory framework is actually applicable and to avoid duplicate testing or misclassification.

Scope: Equipment, component, or stationary facility

The scope of the EMC Directive consistently distinguishes between the device as a standalone functional unit and the fixed installation, which is individually assembled and installed at a specific location. Anyone who, as a distributor, places a mass-produced control cabinet on the market must affix the CE marking and issue an EU Declaration of Conformity. The same obligation applies to a custom-designed switchgear assembly that is conceived as a mass-produced product. If, on the other hand, the control cabinet is permanently integrated into a production facility and assembled exclusively at the installation site, documented good engineering practice applies instead, without a CE marking requirement for the system as a whole—the conformity of individual installed devices remains unaffected. In practice, this distinction often leads to misclassifications: If a system that is actually stationary is mistakenly treated as a device, the required technical documentation may be missing at the installation site. Conversely, if a device that is actually subject to CE marking is declared to be part of a stationary system, market surveillance authorities may issue complaints or even impose sales bans.

Switchgear assemblies as equipment within the meaning of the EMC Directive

Low-voltage switchgear assemblies are primarily considered equipment within the meaning of the Low-Voltage Directive and operate within the same rated voltage range that DIN EN 60204-1 specifies as the upper limit for the electrical equipment of machines —up to 1,000 V AC or 1,500 V DC. In addition to the Low-Voltage Directive, they must independently meet the requirements of the EMC Directive; both legal frameworks apply in parallel, not alternatively, so it is not an either/or situation. To clarify EMC responsibilities, the “black box” concept according to DIN EN 61439 has proven effective; it considers the switchgear assembly through four interfaces: grid connection, installation conditions, outgoing circuits, and operation and maintenance. Each of these interfaces represents a distinct area of responsibility, allowing electromagnetic interactions to be clearly assigned rather than remaining ambiguous between the manufacturer and the operator. Since November 2014, DIN EN 61439 has completely replaced the earlier DIN EN 60439; EMC requirements are not addressed separately in this standard but are included as an integral part of the type approval. For design engineers, this means that electromagnetic compatibility must be factored into the design from the very beginning.

Fixed Installations: Documentation Instead of CE Marking

If a switchgear system is installed as a stationary system, it is exempt from CE marking and the EU Declaration of Conformity under the EMC Directive; however, the duty of care during installation still applies. Good engineering practice is the guiding principle, and the component manufacturers’ specifications regarding intended use must be strictly adhered to. The Declaration of Conformity is replaced by technical documentation, which must include three elements: evidence of the EMC measures implemented, the designation of a responsible person, and the retention of the documentation for the entire operational life of the system. In terms of content, this documentation is based on the measures actually implemented in the control cabinet—such as the grounding concept, equipotential bonding, the shielding of shielded cables, and structured cable routing by zones. If the system remains unchanged, the documentation remains valid. However, this is not the case with structural modifications: alterations, expansions, or the replacement of interference-prone components—such as frequency converters —require a reassessment of the EMC situation, as these changes can fundamentally alter the electromagnetic conditions.

Component Installation: When EMC Verification Must Be Performed Again

In practice, the CE marking on individual components does not automatically replace the EMC certification for the entire assembly. Although DIN EN 60204-1 stipulates that immunity and emission tests may be omitted if all installed components already bear the appropriate CE marking, these tests must still be performed if the marking is not complete. The reason lies in the system-level effects: It is only the interaction of cable routing, a common power supply, and enclosure design that creates new interference paths that do not occur with individual components. Typical examples include frequency converters without mains filters, unshielded motor cables, or a mixture of power and signal wiring in the same cable conduit. As a harmonized standard, DIN EN 60204-1, when applied, establishes a presumption of conformity for electrical equipment under the Machinery Directive 2006/42/EC; however, this does not exempt manufacturers from the obligation to comply with the manufacturer’s specifications regarding the installation conditions of the individual components. These requirements are binding, as they are a prerequisite for the validity of the respective component conformity—if they are deviated from, a new EMC verification of the entire system is required.

Protection Objectives: Emission Limits and Immunity

The two core requirements of the EMC Directive can be clearly distinguished from a technical standpoint: Emission refers to the electromagnetic energy that a piece of equipment generates itself and radiates into the environment via conductors or radiation, as regulated by the base standards DIN EN 61000-6-3 and DIN EN 61000-6-4. Conversely, immunity describes a piece of equipment’s resistance to external influences and is defined in DIN EN 61000-6-1 for industrial applications and in DIN EN 61000-6-2 for residential applications. Electromagnetic interference is transmitted via four coupling mechanisms: galvanically via common conductors, capacitively via electric fields, inductively via magnetic fields, and radiatively via high-frequency fields—wherein conducted and radiated phenomena can be distinguished. In control cabinet construction, typical sources include the clock frequencies of variable-frequency drives and switching power supplies, the switching operations of contactors, and long motor cables, which can act as antenna structures. EMC is not a characteristic that can be verified retrospectively, but is achieved through design—via the cabinet structure, shielding connections, and targeted filtering already during the planning phase.

Electromagnetic Interference: Limits and Types of Emissions

When verifying interference emissions, a distinction is made between conducted emissions, which are transmitted via power and signal lines, and radiated emissions, which are emitted as a field. For conducted emissions, the interference voltage is measured in dBµV; for radiated emissions, the interference field strength is measured in dBµV/m, in each case within defined frequency ranges and evaluated using the quasi-peak and average detectors. However, the specific numerical values of these limits are not specified by the directive itself but by the harmonized generic standards, and the permissible values also vary depending on the respective environmental class. In practical applications within the control cabinet, this results in several mitigation measures: A line filter should be placed as close as possible to the source of interference—for example, directly on the frequency converter—so that interference currents cannot first be radiated over longer sections of cable. Shielding connections must be short and cover a large area; power and signal lines must be routed in separate cable channels, and the mounting plate must be connected to the enclosure via a conductive metal path—i.e., free of insulating paint—to ensure a low-impedance path for high-frequency interference components. Zoning within the control cabinet itself has also proven effective: a power section with frequency converters and contactors, a control section with PLCs and communication components, and a signal section with analog inputs and fieldbus, whereby cables from the power section should under no circumstances be routed through the signal section. Power and control cables should be routed at least 10 cm apart and ideally cross at a 90° angle rather than running parallel, while shielded cables must always be connected to the shield busbar with a full-surface 360° shield connection rather than a single “pigtail” wire. In addition, a star-shaped equipotential bonding system with wide copper busbars instead of thin wires ensures low-impedance current paths, while interference suppression chokes on frequency converters, RC circuits on contactors, and varistors on coils further attenuate high-frequency and inductive interference spikes.

Immunity: Typical EMC Tests

The immunity of a control cabinet is verified using the EN 61000-4 test suite, which provides specific test methods for various disturbance mechanisms. These include electrostatic discharge (ESD), fast transient disturbances (bursts), surge voltages, radiated high-frequency fields, and conducted RF interference. In addition, power-frequency magnetic fields, voltage dips, and short-duration interruptions are tested, as these occur regularly in industrial environments. Each test is conducted at a defined severity level, which determines the simulated stress level and increases in stages. The behavior of the device under test during and after exposure is then classified according to evaluation criteria A through D: Criterion A represents undisturbed operation, while Criterion D represents a permanent loss of function without the possibility of self-recovery. In the control cabinet, control elements, door contacts, and analog inputs are considered particularly critical, as they are directly connected to the outside world and can allow disturbances to couple in directly. The test severity to be applied in each individual case always depends on the intended operating environment—a control cabinet in an industrial setting with frequency converters requires higher test levels than a system in a residential setting.

Environmental Classes: Residential Versus Industrial Environments

Assigning the correct environmental class is a prerequisite for selecting the appropriate base standards: For immunity, DIN EN 61000-6-1 applies in residential, commercial, and industrial areas, whereas DIN EN 61000-6-2 applies to industrial areas—the situation is reversed when it comes to emission limits; here, the requirements in residential areas are more stringent, as the immunity of neighboring equipment is expected to be lower there. In industrial environments, on the other hand, higher interference levels are permitted; however, stricter requirements for immunity are imposed because stronger sources of interference, such as frequency converters or welding systems, are to be expected there. Several criteria are used for classification: connection to the public low-voltage grid indicates a residential area, while the presence of a dedicated substation typically indicates an industrial environment. Proximity to radio reception facilities must also be taken into account, as this can result in increased requirements for interference emissions. For purchasers, the following applies: The environmental class must be determined before selecting a standard and must be clearly justified in the technical documentation, as both the applicable base standard and the relevant test severity levels are derived from it.

Harmonized Standards and Presumption of Conformity

Since the text of the directive itself does not specify technical numerical values, harmonized standards serve to translate the abstract protection objectives of Directive 2014/30/EU into concrete limit values, test procedures, and measurement conditions. If a standard listed in the Official Journal of the European Union is applied in full and without deviation, the so-called “presumption of conformity” applies: The manufacturer may then assume that the relevant essential requirements are met without having to provide separate proof. Within this set of standards, a clear hierarchy applies: General technical standards, such as the DIN EN 61000-6 series, define general requirements for each environmental class, while measurement standards applicable across product families, such as EN 55022 (CISPR 22), specify the measurement methodology for high-frequency emissions; Product family standards further specify these requirements for certain groups of devices, and product-specific standards take precedence over both, if they exist—the most specific applicable standard always takes precedence over the more general generic standard. Since the European Commission continuously updates the lists of standards through implementing decisions, successor standards may replace earlier versions, and individual standards may be withdrawn—often accompanied by temporary transition periods to ensure grandfathering provisions. An outdated list of standards or the use of unlisted standards does not establish a presumption of conformity and instead requires independent technical evidence of compliance. Design professionals should therefore verify the current reference before each project.

EN 61000-6-2: Immunity for Industrial Environments

The scope of DIN EN 61000-6-2 applies to industrial environments: It covers equipment operated at industrial sites with their own transformer stations or medium-voltage power supply and addresses disturbance phenomena such as electrostatic discharge, bursts, surges, and radiated and conducted RF interference. Compared to residential environments, the test severity levels are significantly higher, as industrial environments are expected to contain stronger sources of interference, such as frequency converters or welding equipment. The evaluation of functional behavior during testing is based on criteria A through D, whereby a distinction must always be made between the different operating states of the test object, as susceptibility to interference can vary depending on the operating state. In control cabinet construction, the standard applies to control cabinets, drive cabinets, and automation components, provided that no more specific product standard is applicable—if such a standard exists, it takes precedence over the general technical standard. It should be noted that DIN EN 61000-6-2 covers only immunity; for emissions, the corresponding basic standard for electromagnetic emissions must be consulted separately, as the two protection objectives are standardized separately.

EN 61000-6-4: Emission Standards for Industrial Environments

As the basic standard for electromagnetic emissions from industrial equipment, EN 61000-6-4 (DIN EN 61000-6-4) defines the permissible emission limits for equipment operated at sites with their own transformer substation or medium-voltage power supply. It thus contrasts with DIN EN 61000-6-3, which applies to residential, commercial, and industrial areas and specifies stricter limits due to the lower immunity of neighboring equipment in those environments. Both conducted and radiated emissions are regulated, with the measurement setups, measurement distances, and detectors defined by the standard, and the limit values increasing or decreasing in a frequency-dependent manner. In practice, this means that systems with frequency converters often only meet the permissible limits with additional filtering measures, since the switching frequencies of the power semiconductors generate broadband interference components. It remains crucial to comply with the installation specifications provided by the respective component manufacturer—such as those regarding filter configuration and cable length—as this is the only way to ensure that the manufacturer’s certified compliance remains valid. If a product-specific standard exists for a group of devices, it takes precedence over the general technical standard.

Selecting Standards and Dealing with Changes to Standards

The first step in selecting a standard is product classification: Only once it has been determined whether the item in question is a device, a component, or a stationary installation can the appropriate set of standards be identified. If a product-specific standard exists, it always takes precedence; if no such standard exists, the generic standard applies based on the environmental class—industrial or residential. Next, it must be verified whether the selected standard is currently listed in the list of harmonized standards in the Official Journal of the European Union, as this is the only way to establish a presumption of conformity. This list is continuously updated, meaning that standards may be replaced or removed. One example is DIN EN 60204-1 (VDE 0113-1): Its sixth edition took effect on June 1, 2019, and, among other things, tightened the requirements for EMC testing and residual current protection compared to the previous edition. When such changes to standards occur, transition periods and coexistence phases must be observed, during which the old and new versions may apply in parallel before the earlier version is finally withdrawn. Once these periods have expired, retroactive documentation is required to bring existing systems into compliance with the current limit values and testing standards. Professional planners should therefore recheck the Official Gazette reference before starting each project, rather than relying on standards researched only once.

Conformity Assessment, Documentation, and CE Marking

The process for obtaining the CE mark follows a clearly structured procedure that begins with product classification, which determines which directives and harmonized standards apply to the specific project. This is followed by the actual EMC assessment, including the corresponding immunity and emission tests, the results of which are incorporated into the technical documentation and documented there in a traceable manner. For devices as defined by the EMC Directive, the law prescribes internal production control as the standard procedure, under which the manufacturer independently assesses and documents conformity; the involvement of a Notified Body remains optional and is chosen in practice only in exceptional cases. If a Notified Body is nevertheless commissioned, its accreditation can be verified via the European Commission’s NANDO database, the official register of Notified Bodies for the entire European Economic Area. The entire conformity assessment procedure is concluded with the preparation of the technical documentation and the EU Declaration of Conformity, as well as the affixing of the CE marking to the finished product. If multiple directives apply to a control cabinet at the same time, all applicable requirements must be covered in a single, joint declaration, rather than creating separate declarations for each directive.

Self-certification through internal production control

Under the standard procedure set forth in Annex II of Directive 2014/30/EU, the manufacturer assesses the electromagnetic compatibility of its control cabinet on its own responsibility: The manufacturer defines the test setup, performs the required immunity and emission tests or has them performed, and documents the results without the mandatory involvement of a Notified Body. Reliable self-certification requires that the relevant harmonized standards be fully applied, that the test reports be structured in a transparent manner, and that the test specimen be examined under representative operating conditions—only in this way can the presumption of conformity be substantiated. Nevertheless, the manufacturer may voluntarily involve a Notified Body, for example, to provide additional assurance for complex systems. In practice, typical weaknesses repeatedly arise in the same areas: Tests conducted on non-representative samples—such as a base model lacking the frequency converters that will actually be installed later—or incomplete application of standards in customer-specific control cabinet variants, where individual equipment configurations differ from the tested configuration. Both of these issues compromise the validity of the self-declaration and can lead to objections during market surveillance.

Contents of the Technical Documentation

For self-certification, Annex II of Directive 2014/30/EU requires the manufacturer to compile complete technical documentation that provides verifiable evidence of the conformity decisions made in the event of market surveillance. The documentation must include a general product description, design and manufacturing drawings, as well as circuit diagrams and component lists, which can be used to reconstruct the specific configuration of the switchgear assembly. In addition, a description of the solutions applied to meet the essential requirements and a list of the harmonized standards used must be included. In addition, the results of design calculations and test reports, as well as the actual EMC assessment, must be included, supplemented by the operating instructions with installation and maintenance guidelines. The EMC Directive expressly stipulates a ten-year retention period from the date of placing on the market; by analogy, a ten-year retention requirement applies to the type examination in accordance with DIN EN 61439 at the manufacturer’s premises. If changes are made to the switchgear assembly after it has been placed on the market, the technical documentation must be updated accordingly so that it continues to accurately reflect the actual configuration.

Further information can be found on the “Control Cabinet Construction: Standards” Hub page. For practical implementation, see also “Control Cabinet Construction.”

How to Properly Issue an EU Declaration of Conformity

The EU Declaration of Conformity must contain certain mandatory information in accordance with Annex IV of Directive 2014/30/EU in order to be recognized as complete evidence for the purposes of market surveillance. These include a unique product identifier—such as a model, lot, or serial number—that allows the document to be linked to a specific control cabinet; the name and address of the manufacturer or its authorized representative; and an explicit statement that the manufacturer bears sole responsibility for conformity. A reference to the harmonized standards applied, including their edition, is also required, as a reference to standards that have already been withdrawn undermines the validity of the declaration. If a notified body is involved, its identification number must be provided; this is followed by the place, date, and a legally binding signature. If the control cabinet is subject to both the Low Voltage Directive 2014/35/EU and the Machinery Directive 2006/42/EC, all relevant requirements are combined into a single declaration, rather than issuing separate documents for each directive. The declaration must be provided in the official language of the country of destination and must accompany the product or be made available upon request. Another common error is the failure to specify the applicable environmental class.

Responsibilities in the Supply Chain and Market Surveillance

In addition to the manufacturer and the authorized representative, the EMVG identifies other parties with their own obligations along the supply chain: The importer brings products from third countries into the European Economic Area and must verify their conformity before placing them on the market, while the authorized representative acts on behalf of a manufacturer based outside the EU in dealings with the authorities, and the distributor generally has fewer obligations when merely reselling products. Crucial for control cabinet manufacturers and system integrators: Anyone who supplies a product under their own name or brand, or who substantially modifies an existing switchgear assembly, automatically assumes the full obligations of a manufacturer —including conformity assessment and technical documentation. Even the replacement of key components or a customer-specific modification can trigger this classification. For stationary systems, operators and installers also have their own due diligence obligations in accordance with good engineering practice. Practical oversight falls to the Federal Network Agency’s market surveillance division, which often takes action in response to specific complaints of radio interference. As part of the investigation process, the agency may first request documentation, then demand corrective measures, and subsequently order product recalls. If violations persist, the manufacturer faces a sales ban and a fine in accordance with the provisions of the law governing administrative offenses.

Obligations of Manufacturers, Importers, and Distributors

Beyond the general division of roles, the obligations of economic operators can be clearly distinguished from one another. The manufacturer bears full responsibility for the conformity assessment, the preparation of the technical documentation and the EU Declaration of Conformity, as well as the affixing of the CE marking; in addition, the manufacturer must provide type and batch identification and indicate the name and contact address on the product or its packaging. Before placing the product on the market, the importer must verify that the manufacturer has actually carried out the required procedures and prepared the prescribed documentation, and may only place compliant products on the market—this must be carefully documented, particularly when sourcing components from third countries. The distributor bears a reduced, but not insignificant, duty of care: They must verify that the marking, declaration of conformity, and accompanying documentation are complete before making a product available. All three parties are subject to obligations of cooperation, information, and traceability with regard to market surveillance. This becomes relevant in practice, for example, with private-label cabinets or when untested components are installed in a complete system without supporting documentation—in such cases, there is a risk of complaints that could lead to a sales ban on the entire combination.

EMC-compliant design as a basis for verification

The EMC-compliant design of a control cabinet can be demonstrated through specific design measures: a consistent grounding and equipotential bonding concept, conductively connected mounting plates and enclosure components, cable shields with large-area contact on both sides, and the physical separation of power and signal wiring. In addition, there are mains and motor filters, interference suppression circuits for inductive loads, and filtering of input and output terminals. For stationary systems, these measures demonstrate documented good engineering practice; for equipment, they validate the test results. Additionally, Section 18 requires testing of the electrical equipment of machines during installation as well as after modifications or repairs; in which case documentation and calculation of the short-circuit current are mandatory, and temperature verifications in accordance with IEC 61439 or IEC 60890 are required to rule out overheating. It also remains crucial that the manufacturer’s specifications regarding installation conditions are adhered to, as they are a prerequisite for the validity of the respective components’ CE marking.

Additional Standards and Services in Control Panel Construction

The EMC Directive does not stand alone in switchgear manufacturing but interacts with other sets of regulations. For switchgear assemblies, DIN EN 61439 applies; its base standard has been structurally revised with the new edition DIN EN IEC 61439-1:2021-10; in Part 2, a minimum protection rating of IPXXB is additionally required for compartments with a subdivision factor greater than 1, where the components remain live even when the functional unit is switched off. For the electrical equipment of machines, DIN EN 60204-1 applies in addition, which, among other things, prescribes a residual current protection of no more than 30 mA for outlet circuits and requires a glow-wire test in the type approval to assess resistance to heat and fire. The protection and impact resistance ratings of enclosures are governed by DIN EN 60529 and DIN EN 62262. In practice, EMC requirements must always be met in parallel with the Low-Voltage Directive and the Machinery Directive; they are never intended to serve as substitutes for one another.

Additional Standards for Control Panel Construction

This page is part of our series on standards. For a comprehensive overview, see the page on standards for control panel construction; details on the other standards are provided below:

Do you need a control cabinet manufactured in accordance with standards? Unitechnik is your partner for control cabinet and switchgear manufacturing —UL-certified for over 50 years.

Your contact persons

Dirk Schütz

Head of Switchgear Construction Department

T +49 2261 987-405
E-Mail | vCard

Felix Trommershausen

Sales Switchgear Construction

T +49 2261 987-413
E-Mail | Linkedin | vCard

FAQ

How does the EMC Directive differ from the Low-Voltage Directive?

The EMC Directive 2014/30/EU and the Low-Voltage Directive 2014/35/EU pursue different safety objectives and apply cumulatively, not alternatively. While the Low-Voltage Directive regulates the electrical safety of equipment in the rated voltage range between 50 V AC and 1,000 V AC or 75 V DC and 1,500 V DC, the EMC Directive addresses electromagnetic compatibility regardless of voltage level. For switchgear assemblies, this means that both directives must be complied with independently. Harmonized standards such as DIN EN IEC 61439 make it possible to demonstrate compliance with both sets of requirements simultaneously and to combine them into a single EU Declaration of Conformity.

Which devices are exempt from the scope of the EMC Directive?

Not all electrical equipment is subject to the EMC Directive 2014/30/EU. Exceptions include areas governed by their own regulations that already incorporate EMC requirements, such as radio equipment under the Radio Equipment Directive 2014/53/EU, motor vehicles under UN/ECE R10, medical devices under the MDR, and specific equipment for aviation, rail, and maritime transport. This distinction is particularly relevant in control panel construction as soon as Wi-Fi, Bluetooth, or cellular modules are installed, as this can affect the legal classification of the entire system. Careful product classification at the start of a project is therefore essential to avoid duplicate testing or misclassification.

Who is responsible for ensuring compliance with the EMC Directive?

The primary responsibility for compliance with the EMC Directive 2014/30/EU lies with the manufacturer, who conducts the conformity assessment, prepares the technical documentation, issues the EU Declaration of Conformity, and affixes the CE marking. These obligations automatically apply as well to anyone who places a product on the market under their own name or makes substantial modifications to an existing switchgear assembly. In addition, other parties have their own obligations:

  • Authorized representative: represents manufacturers based outside the EU in dealings with authorities
  • Importer: verifies conformity before placing the product on the market
  • Distributor: verifies the marking and accompanying documentation upon making the product available

For fixed installations, operators and installers also have their own due diligence obligations in accordance with good engineering practice. Oversight is carried out by the Federal Network Agency as the market surveillance authority.

What requirements does the EMC Directive impose on electrical equipment?

The EMC Directive 2014/30/EU requires electrical equipment to meet two key criteria: limited emission of interference and sufficient immunity to interference. The directive itself does not specify concrete numerical values but rather formulates these protection objectives in a technology-neutral manner in Annex I. The specific requirements are defined by harmonized standards, such as the DIN EN 61000-6 series. If a piece of equipment meets these requirements, the manufacturer affixes the CE marking.

What does EMC mean in the context of electrical devices?

EMC stands for electromagnetic compatibility and describes the ability of electrical equipment to function as intended in its electromagnetic environment without causing unacceptable interference to other devices. This gives rise to two technical protection objectives:

  • Limited interference emissions: The device must generate electromagnetic interference only to an extent that does not impair the operation of radio, telecommunications, or other equipment.
  • Sufficient immunity: The device must be resistant to external electromagnetic influences.

These requirements form the core of the EMC Directive 2014/30/EU and are technically specified by harmonized standards, as the text of the directive itself does not contain any specific limit values.

What is the number of the current EU EMC directive?

The currently applicable European Union EMC Directive is numbered 2014/30/EU and supersedes the earlier Directive 2004/108/EC. For control cabinet construction, it is also important to note that other legal acts may apply in parallel, such as the Low-Voltage Directive 2014/35/EU or the Machinery Directive 2006/42/EC, which complement the EMC Directive without replacing it. The numbering system, which follows the pattern “Year/Number/Type of Legal Act,” is standardized throughout the EU and allows for unambiguous identification in the Official Journal as well as in declarations of conformity, in which the full designation, including the year, must always be specified.

What is the EMC Directive, and to which products does it apply?

The EMC Directive 2014/30/EU is the central EU legal act governing electromagnetic compatibility. It stipulates that equipment must function as intended in its electromagnetic environment without causing unacceptable interference to other devices. This gives rise to two protection objectives: limited emission of interference and sufficient immunity to interference. It generally applies to all equipment that can cause electromagnetic interference or be affected by it, such as devices, components, and fixed installations. Exceptions include, among others, radio equipment, which is instead subject to the Radio Equipment Directive, as well as certain sector-specific products such as motor vehicles, medical devices, or specific equipment for aviation, rail, and maritime transport. In Germany, the directive was transposed into national law by the EMVG.

What transition periods applied when the current EMC Directive was introduced?

The current Directive 2014/30/EU replaced the previous Directive 2004/108/EC and was transposed into German law through the EMVG. DIN EN 60204-1 is relevant for the change in standards regarding the electrical equipment of machines; its current version contains requirements for EMC testing. Design engineers should check the current Official Journal reference for the harmonized standards before starting any project, as only fully applied, listed standards establish a presumption of conformity.

What role do notified bodies play in EMC conformity assessment?

In the EMC conformity assessment, the involvement of a notified body is not mandatory but optional, as the standard procedure is internal production control in accordance with Annex II. Annex III also sets forth a procedure involving a Notified Body, which may be particularly relevant for types of products for which no harmonized standards—or only partially harmonized standards—have been applied. The Federal Network Agency is responsible for notification and market surveillance within the German legal jurisdiction.

What are the potential consequences of violating the EMC Directive?

In the event of violations of the EMC Directive 2014/30/EU or the national EMC Act, the Federal Network Agency, as the competent market surveillance authority, may take graduated measures. These include, in particular:

  • Request for documentation and technical evidence
  • Requests to rectify the product
  • Ordering recalls of equipment already delivered
  • Prohibiting the sale of non-compliant products
  • Imposing fines for administrative offenses—such as missing labeling, incomplete documentation, or failure to cooperate—the amount of which depends on the severity of the violation

The starting point for an inspection procedure is often specific complaints of radio interference. Economic operators in the supply chain—that is, manufacturers, authorized representatives, importers, and distributors—also have specific obligations to cooperate with and provide information to the authority.

What documentation does the EMC Directive require manufacturers to provide?

The EMC Directive 2014/30/EU requires manufacturers to provide complete technical documentation that allows for the verification of conformity decisions during market surveillance. For switchgear assemblies, this evidence is based on the measures actually implemented in the control cabinet—such as the grounding concept, equipotential bonding, the shielding of shielded cables, and structured cable routing by zone. For stationary installations, the declaration of conformity is replaced by technical documentation that must include three elements: evidence of the EMC measures applied, the designation of a responsible person, and the retention of the documentation for the entire operational life of the installation. In the event of subsequent changes—such as modifications, expansions, or the replacement of interference-prone components like frequency converters—the documentation must be updated accordingly, or the EMC situation must be reassessed.

What conformity assessment procedures are specified under the EMC Directive?

The EMC Directive 2014/30/EU provides for the conformity assessment procedures set forth in Annexes II and III. It thus follows the structure of the New Legislative Framework and establishes obligations for manufacturers, authorized representatives, and importers. The process always concludes with technical documentation, an EU Declaration of Conformity, and CE marking.

What role does the CE marking play in relation to the EMC Directive?

The CE marking is the visible result of the conformity assessment procedure under the EMC Directive 2014/30/EU. The manufacturer affixes it to the product only after verifying, as part of its internal production control, that the product’s emissions and immunity meet the essential requirements and that the technical documentation and the EU Declaration of Conformity are complete. The manufacturer thus declares, on its own responsibility, that all relevant requirements have been met.

If other directives, such as the Low Voltage Directive or the Machinery Directive, also apply to a control cabinet, the CE marking always cumulatively covers all applicable requirements. For stationary installations, the CE marking requirement does not apply; in such cases, documented good engineering practice takes its place.

What is meant by "emitted interference" as defined in the EMC Directive?

In accordance with the EMC Directive 2014/30/EU, electromagnetic emissions refer to the electromagnetic energy that a piece of equipment generates itself and radiates into its surroundings via conductors or as radiation. A distinction is made between conducted emissions, measured as interference voltage in dBµV, and radiated emissions, measured as interference field strength in dBµV/m. Typical sources in a control cabinet include the switching frequencies of variable-frequency drives, switching power supplies, and long motor cables. Measures such as closely positioned power line filters, short shield connections, and separate cable routing are used to limit these emissions, ensuring that the equipment does not interfere with the intended operation of other devices.

Which harmonized standards are applied under the EMC Directive?

The essential requirements of Directive 2014/30/EU deliberately do not include specific numerical values. This task is handled by harmonized standards, which are listed in the Official Journal of the EU and translate the protection objectives into limit values, test procedures, and measurement conditions. A hierarchy of standards applies:

  • General technical standards, such as the DIN EN 61000-6 series, specify general requirements for each environmental class.
  • Product family standards specify these requirements for specific groups of devices.
  • Product-specific standards take precedence over both, if they exist.

If a listed standard is applied in full, a presumption of conformity arises. Since the European Commission continuously updates the lists of standards through implementing decisions, current references must be checked before each project, as outdated or unlisted standards do not establish a presumption of conformity.